Product Features: Residual current circuit breakers (RCCBs) offer personal and property protection as well as protection against electrically ignited fires according to DIN VDE 0100-410 and DIN VDE 0100-530. The F200 series residual current circuit breakers ensure protection against sinusoidal AC currents and pulsating currents against earth. As well as error protection (protection against indirect touch), additional protection (with I?n ? 30 mA) and fire protection (with I?n ? 300mA) They meet the product standards for RCDs type A IEC/EN 61008-1, 61008-2-1, 61543 (VDE 0664 10, 11, 30) and for type F DIN EN 62423 (VDE 0664-40). Areas of application are household, commercial and industrial applications. The extensive range of accessories provides you with everything you need for your installation tasks. Optimal compromise between safety and operational continuity thanks to the anti-interference resistance against unwanted triggering and 10 ms short time delay. The F200 F are mixed frequency sensitive especially for single-phase electronic consumers with frequency converters, with a frequency range of 0...1 kHz to detect the residual current and additionally detect pulsating residual currents with a DC component up to 10 mA. Technical details: Mounting type: DIN rail. Installation depth: 69 mm. Rated current: 63 A. Rated voltage: 400 V. Number of poles: 4. Rated residual current 0.03 pendelleuc Residual Current Type Other Short circuit resistance (ICW) 1 kA. Shock resistance 4 kA. Width in division units 4 Short-term delayed type: yes. Protection class (IP) IP2X. Additional equipment possible: yes. Number of poles 4 rated current [A]63Fi typeFEsensitivity30mA